3.2 Number of Power Cable Cores

3.2.1 Where the neutral of power sporce of 1kV or below is solidly grounded,the number of cable cores for the three-phase circuit shall be determined in accordance with the following requirements:

1 Where the protective wire is grounded by connecting with the exposed conductive parts of energized equipment,the following requirements shall be met:

1)If the protective wire and the neutral line share the same conductor,four-core cables shall be used.

2)If the protective wire is independent of the neutral line,five-core cables should be used;however,four-core cables together with an additional protective conductor may be used provided that the requirements of Article 5.1.16 of this code are met.

2 Where the earth of exposed conductive parts of energized equipment is independent of that of the power supply system,four-core cables shall be used.

3.2.2 Where the neutral of power supplies of 1kV or below is solidly grounded,the number of cable cores for single-phase circuits shall be selected in accordance with the following requirements:

1 Where the protective wire is grounded by connecting with the exposed conductive parts of energized equipment,the following requirements shall be met:

1)If the protective wire and the neutral line share the same conductor,two-core cables shall be used.

2)If the protective wire is independent of the neutral line,three-core cables should be used;however,two-core cables together with an additional protective conductor may be used provided that the requirements of Article 5.1.16 of this code are met.

2 Where the earth of exposed conductive parts of energized equipment is independent of that of the power supply system,two-core cables shall be used.

3.2.3 The number of cable cores for 3-35kV three-phase power supply circuits shall be selected according to the following requirements:

1 For circuits with a large working current or cables laid underwater,three single-core cables may be used for each circuit.

2 In other cases,three-core cables of ordinary belted type shall be used,or alternatively,three single-core cables in stranded configuration may be used.

3.2.4 For 110kV three-phase power supply circuits,three single-core cables may be used for each circuit,except for cables laid underwater in lakes or seas and with small cable cross sections,in which case three single-core cables may be used.

For three-phase power supply circuits of 110kV or above,three single-core cables shall be used for each circuit.

3.2.5 For HV AC single-phase power supply circuits such as that for electric railways,two-core cables or two single-core cables shall be used for each circuit.

3.2.6 The number of cable cores for DC power supply circuits shall be selected according to the following requirements:

1 For LV DC power supply circuits,two-core cables should be used,and single-core cables may be used as an alternative.

2 For HV DC transmission systems,single-core should be used,and coaxial two-core cables may be used when laid underwater in lakes and seas.